12.2.3.3 X2 PROFINET
Data Transmission Rate and Cables
For PROFINET, you require a data transmission rate of 100 Mbit/s (Fast Ethernet). The interfaces
are designed for full-duplex mode; in other words, the ports can both transmit and receive. For
data transfer purposes you can use electrical twisted copper cables (twisted pair, 4-wire,
100Base-T):
The transmission characteristics of these cables must meet the requirements of CAT5.
The maximum length of the connections between the end device and network component
or between two network components (e.g. switch ports) must not exceed 100 m.
Pin assignment
Table 12-16 PROFINET interfaces X2, ports 1, 2
Pin Signal name Signal type Meaning
1 TX+ O Transmit data +
2 TX- O Transmit data -
3 RX+ I Receive data +
4 N.C. - Reserved, do not use
5 N.C. - Reserved, do not use
6 RX- I Receive data -
7 N.C. - Reserved, do not use
8 N.C. - Reserved, do not use
Cable speci󹪝cation
Table 12-17 Cable speci󹪝cation at X2, ports 1, 2
Characteristic Version
Connector type RJ45 socket
Cable type Industrial Ethernet cable (as of CAT5)
Max. cable length 100 m
LED displays
For diagnostic purposes, the RJ45 sockets are each equipped with a green and a yellow LED. This
allows the following information to be displayed for the respective PROFINET port:
Table 12-18 PROFINET ports LED displays
Name Color Status Meaning
Link Green lit Transfer rate 100 Mbit/s
o󹪜 No or faulty connection