NOTICE
Ensuring the function of the digital inputs
An open input is interpreted as "low".
Only "rapid inputs" can be used as inputs for BEROs and probes.
Terminals M1 or M2 must be connected for the digital inputs to work. This can be done as
follows:
Connect the ground reference of the digital inputs.
A jumper to terminal M (note that these digital inputs are then no longer electrically
isolated).
Note
For a transient (brief) voltage interruption of the 24 V supply, the digital outputs are switched
inactive for this time.
8.11 USB
Table 8-25 Cable speci󹪝cation for X125 and X135
Characteristics Versions
Connector type Double USB socket – type A
Version USB 3.0
Current carrying capacity 0.9 A per channel
Max. cable length 3 m
Note
The 5 V power supply is designed to be short-circuit proof.
Connecting
8.11 USB
NCU 1740
Equipment Manual, 10/2021, A5E51087503B AA 87