EasyManuals Logo
Home>Siemens>Relays>siprotec 7SD5

Siemens siprotec 7SD5 User Manual

Siemens siprotec 7SD5
698 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #119 background imageLoading...
Page #119 background image
2.5 Distance Protection
119
7SD5 Manual
C53000-G1176-C169-1
The calculation of the phase-phase loop does not take place as long as one of the con-
cerned phases is switched off (during single-pole dead time), to avoid an incorrect
measurement with the undefined measured values existing during this state. A state
recognition (refer to Section 2.23.1) provides the corresponding block signal. A logic
block diagram of the phase-phase measuring system is shown in Figure 2-34.
Figure 2-34 Logic for a phase–phase measuring unit
Phase–Earth Loops For the calculation of the phase-earth loop, for example during a L3-E (Figure 2-35) it
must be noted that the impedance of the earth return path does not correspond to the
impedance of the phase. In the loop equation
I
L3
· Z
L
– I
E
· Z
E
= U
L3-E
Z
E
is replaced by (Z
E
/Z
L
) · Z
L
yielding:
From this the line impedance can be extracted
Figure 2-35 Short-circuit of a phase-earth loop
The factor Z
E
/Z
L
solely depends on the line parameters and not on the fault distance.
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens siprotec 7SD5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SD5 and is the answer not in the manual?

Siemens siprotec 7SD5 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SD5
CategoryRelays
LanguageEnglish

Related product manuals