EasyManua.ls Logo

Siemens siprotec 7SD5

Siemens siprotec 7SD5
698 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Functions
172
7SD5 Manual
C53000-G1176-C169-1
Figure 2-65 Logic diagram of power swing detection
In Figure 2-65 a simplified logic diagram for the power swing function is given. This
measurement is done on a per phase basis although Figure 2-65 only shows the logic
for one phase. Before a power swing detected signal is generated, the measured im-
pedance must be inside the power swing polygon (PPOL).
In the following there are 4 measuring criteria:
Trajectory continuity The calculated R and X values must create a constant
line. There must be no jump from one measured value
to the next. Refer to Figure 2-63.
Trajectory monotony The impedance trajectory must initially not change R-
direction. Refer to Figure 2-63.
Trajectory symmetry The trajectory of each phase is evaluated. If no fault is
present these 3 trajectories must be symmetrical.
During single pole open conditions the remaining 2 tra-
jectories must be symmetrical.
Trajectory stability When the impedance trajectory enters the PPOL
during a swing condition, the system must be in the
area of steady state instability. In Figure 2-64 this cor-
responds to the lower half of the circle.
All these conditions must be true for the generation of a power swing block condition.
Once the power swing block condition is set it will remain picked up until the imped-
ance vector leaves the power swing polygon (PPOL). This is unless a fault occurs
during this phase. The detection of a jump in the trajectory or non-symmetry of the tra-
jectories will reset the power swing blocking condition. The power swing detection can
be blocked via a binary input.
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens siprotec 7SD5

Related product manuals