Functions
132
7SS52 V4 Manual
C53000-G1176-C182-3
5.3.7 Settings for the Central Unit
Addr. Setting Title Setting Options Default Setting Comments
114 BF BI MODE 1-ch w/o sup
1-ch w sup
2-ch w/o sup
2-ch w sup
1-ch w sup Binary input mode / supervision
BF
115 BF OP MODE non existent
external
BZ unbalance
trip rep/unbal
I>query
trip rep/I>quer
BZ unbalance Operation mode BF
116 BF I< ON
OFF
OFF Low-current mode BF
117 TRIP REP. MODE 1pole
3pole
1pole TRIP repeat mode
118 I> BF 0.10 .. 2.00 I / In 0.50 I / In Current threshold for BF
119 I> BF-EF 0.05 .. 2.00 I / In 0.25 I / In Current threshold for BF - EF
120 T-BF-1P 0.05 .. 10.00 s 0.25 s Time delay for BF with 1-pole
faults
121 T-BF-mP 0.05 .. 10.00 s 0.25 s Time delay for BF with multi-pole
faults
122 T-BF I< 0.05 .. 10.00 s 0.25 s Time delay for BF low current
mode
123A T-BF IMP 0.05 .. 10.00 s 0.50 s Time delay for BF pulse mode
124 T-BF CB fault 0.00 .. 10.00 s 0.10 s Time delay BF after CB fault
125 T-TRIP repeat 0.00 .. 10.00 s 0.12 s Time delay for TRIP repeat
127 T-BF rel sup 0.02 .. 15.00 s 15.00 s Supervision bin. input BF-re-
lease
128 T-BF 2chan 0.06 .. 1.00 s 0.06 s Supervision time BF start / re-
lease
6106 Tmin TRIP 0.01 .. 32.00 s 0.15 s Minimum duration of TRIP com-
mand
6320A EF charact. released
blocked
blocked Earth fault characteristic switch-
over
www . ElectricalPartManuals . com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SS525 V3.3 and is the answer not in the manual?

Siemens SIPROTEC 7SS525 V3.3 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SS525 V3.3
CategoryPower distribution unit
LanguageEnglish

Related product manuals