Connection Method
27
7SS52 V4 Manual
C53000-G1176-C182-3
2.3.2.3 D-SUB Female Connectors
Connectors The serial ports of the central unit and of the bay units have 9-pole D-SUB female con-
nectors. The serial ports include:
the PC port at the front of the central unit and the bay unit
the service port at the back of the central unit
the system port at the back of the central unit
the clock synchronization interface at the back of the central unit
For assignment of the connectors, please refer to the Figures A-3, page 342 and A-5,
page 345 in the Appendix.
Connection method You can use any standard 9-pole D-SUB plug connectors per MIL-C-24308 and
DIN 41652.
Depending on the device version, the pin assignment is the same as for an RS232 or
RS485 port.
You can use for connection e.g. a 5-strand, shielded interface cable.
Tools No tools are required for connection the interface cables.
2.3.2.4 Fiber-Optic Cable Connections
Central unit Depending on the variant ordered, the service and the system port on the rear of the
central unit may have additional fiber-optic connections (Figure 2-6, page 22).
Moreover, the central unit is connected with the bay units by fiber-optic cables. The
bay unit connectors are located on the back of the central unit (Figure 2-6, page 22).
Bay units Depending on the mounting variant, the fiber-optic interface to the central unit is locat-
ed on the bottom (Figure 2-7, page 23) or the rear (Figure 2-8, page 24) of the bay
unit. For assignment of the connectors, please refer to Figure A-4, page 343 in the Ap-
pendix.
Connection method FO connector type: ST connector
Use fiber type: Multimode FO,
G50/125 µm,
G62.5/125 µm,
G100/140 µm
for wave length: λ approx. 820 nm