4 Technical Data
298
7UM61 Manual
C53000-G1176-C127-3
Service / Modem Interface
System Interface
Connection isolated interface for data transfer
Operation with DIGSI
®
4
Transmission Speed min. 4 800 Baud; max. 115 200 Baud
Factory Setting: 38,400 Baud
Parity: 8E1
RS232/RS485 RS232/RS485 according to the order-
ing variant
Connection for flush-
mounted case
rear panel, slot "C", 9-pin DSUB
socket
Surface-mounting case In the housing on the case bottom;
shielded data cable
Test voltage 500 VAC
RS232
bridgeable distance 15 m
RS485
bridgeable distance 1,000 m
IEC 60 870-5-103
RS232/RS485
acc. to ordered version
isolated interface for data transfer to a
master terminal
RS232
Connection for flush-
mounted case
rear panel, slot "B", 9-pin D-SUB
socket
for surface-mounted case in console housing at case bottom
Test voltage 500 VAC
Transmission Speed min. 4,800 Baud; max. 200 Baud
Factory setting 38,400 Baud
bridgeable distance 15 m
RS485
Connection for flush-
mounted case
rear panel, slot "B", 9-pin D-SUB
socket
for surface-mounted case in console housing at bottom side I
Test voltage 500 VAC
Transmission Speed min. 4,800 Baud; max. 115,200 Baud
Factory setting 38,400 Baud
bridgeable distance max. 1 km (0.6 miles)