4.1 General
299
7UM61 Manual
C53000-G1176-C127-3
Fibre optic cable (FO)
Fibre optic connector type ST connector
Connection for flush-
mounted case
rear panel, mounting location "B"
for surface-mounted case in console housing at case bottom
optical wavelength λ = 820 nm
Laser Class 1 according to
EN 60825–1/–2
Using glass fibre 50/125 µm or using
glass fibre 62.5/125 µm
admissible link signal at-
tenuation
max. 8 dB, with glass fibre 62.5/125
µm
bridgeable distance max. 1.5 km (0.6 miles)
Character idle state configurable; factory setting "Light off"
Profibus RS 485 (FMS and
DP)
Connection for flush-
mounted case
rear panel, slot "B", 9-pin D-SUB
socket
for surface-mounted case in console housing at case bottom
Test voltage 500 VAC
Transmission Speed up to 12 MBd
bridgeable distance 1,000 m / 3300 feet at 93.75 kBd
500 m / 1666 feet at 187.5 kBd
200 m/ 660 feet at 1.5 MBd
100 m/ 330 feet at 12 MBd
DPN3.0 RS485
Connection for flush-
mounted case
rear panel, slot "B", 9-pin D-SUB
socket
for surface-mounted case in console housing at case bottom
Test voltage 500 VAC
Transmission Speed up to 19200 Bd
bridgeable distance max. 1,000 m (3300 feet)
MODBUS RS485
Connection for flush-
mounted case
rear panel, slot "B", 9-pin D-SUB
socket
for surface-mounted case in console housing at bottom side
Test voltage 500 VAC
Transmission Speed up to 19200 Bd
bridgeable distance max. 1,000 m (3300 feet)