A.7 Settings
385
7UM61 Manual
C53000-G1176-C127-3
5106 IEE< Sens. E Fault 1.5 .. 50.0 mA; 0 0.0 mA Iee< Pickup (Interrupted Circuit)
5201 SEF 3rd HARM. SEF 3.Harm. OFF
ON
Block relay
OFF Stator Earth Fault Protection
3rdHarm.
5202 U0 3.HARM< SEF 3.Harm. 0.2 .. 40.0 V 1.0 V U0 3rd Harmonic< Pickup
5203 U0 3.HARM> SEF 3.Harm. 0.2 .. 40.0 V 2.0 V U0 3rd Harmonic> Pickup
5204 T SEF 3. HARM. SEF 3.Harm. 0.00 .. 60.00 sec; 0.50 sec T SEF 3rd Harmonic Time Delay
5205 P min > SEF 3.Harm. 10 .. 100 %; 0 40 % Release Threshold Pmin>
5206 U1 min > SEF 3.Harm. 50.0 .. 125.0 V; 0 80.0 V Release Threshold U1min>
6501 STARTUP MOTOR Start Motor OFF
ON
Block relay
OFF Motor Starting Time Supervision
6502 START. CURRENT Start Motor 1A 0.10 .. 16.00 A 3.12 A Starting Current of Motor
5A 0.50 .. 80.00 A 15.60 A
6503 STARTING TIME Start Motor 1.0 .. 180.0 sec 8.5 sec Starting Time of Motor
6504 LOCK ROTOR TIME Start Motor 0.5 .. 120.0 sec; 6.0 sec Permissible Locked Rotor Time
6505 I MOTOR START Start Motor 1A 0.60 .. 10.00 A 1.60 A Current Pickup Value of Motor
Starting
5A 3.00 .. 50.00 A 8.00 A
6601 RESTART INHIBIT Restart Motor OFF
ON
Block relay
OFF Restart Inhibit for Motors
6602 IStart/IMOTnom Restart Motor 1.5 .. 10.0 4.9 I Start / I Motor nominal
6603 T START MAX Restart Motor 3.0 .. 320.0 sec 8.5 sec Maximum Permissible Starting
Time
6604 T EQUAL Restart Motor 0.0 .. 320.0 min 1.0 min Temperature Equalization Time
6606 MAX.WARM STARTS Restart Motor 1 .. 4 2 Permissible Number of Warm
Starts
6607 #COLD-#WARM Restart Motor 1 .. 2 1 Number of Cold Starts - Warm
Starts
6608 Kτ at STOP Restart Motor 1.0 .. 100.0 5.0 Extension of Time Constant at
Stop
6609 Kτ at RUNNING Restart Motor 1.0 .. 100.0 2.0 Extension of Time Constant at
Running
6610 T MIN. INHIBIT Restart Motor 0.2 .. 120.0 min 6.0 min Minimum Restart Inhibit Time
7001 BREAKER FAILURE Breaker Failure OFF
ON
Block relay
OFF Breaker Failure Protection
7002 TRIP INTERN Breaker Failure OFF
BO3
CFC
OFF Start with Internal TRIP
Command
7003 CIRC. BR. I> Breaker Failure 1A 0.04 .. 2.00 A 0.20 A Supervision Current Pickup
5A 0.20 .. 10.00 A 1.00 A
7004 TRIP-Timer Breaker Failure 0.06 .. 60.00 sec; 0.25 sec TRIP-Timer
7101 INADVERT. EN. Inadvert. En. OFF
ON
Block relay
OFF Inadvertent Energisation
7102 I STAGE Inadvert. En. 1A 0.1 .. 20.0 A; 0.3 A I Stage Pickup
5A 0.5 .. 100.0 A; 1.5 A
7103 RELEASE U1< Inadvert. En. 10.0 .. 125.0 V; 0 50.0 V Release Threshold U1<
7104 PICK UP T U1< Inadvert. En. 0.00 .. 60.00 sec; 5.00 sec Pickup Time Delay T U1<
7105 DROP OUT T U1< Inadvert. En. 0.00 .. 60.00 sec; 1.00 sec Drop Out Time Delay T U1<
7110 FltDisp.LED/LCD Device Target on PU
Target on TRIP
Target on PU Fault Display on LED / LCD
8001 FUSE FAIL MON. Measurem.Superv OFF
ON
OFF Fuse Failure Monitor
8101 MEASURE. SUPERV Measurem.Superv OFF
ON
OFF Measurement Supervision
8102 BALANCE U-LIMIT Measurem.Superv 10 .. 100 V 50 V Voltage Threshold for Balance
Monitoring
8103 BAL. FACTOR U Measurem.Superv 0.58 .. 0.90 0.75 Balance Factor for Voltage
Monitor