C53000-G1176-C127-3
8104 BALANCE I LIMIT Measurem.Superv 1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor
5A 0.50 .. 5.00 A 2.50 A
8105 BAL. FACTOR I Measurem.Superv 0.10 .. 0.90 0.50 Balance Factor for Current
Monitor
8106 ΣI THRESHOLD Measurem.Superv 1A 0.05 .. 2.00 A 0.10 A Summated Current Monitoring
Threshold
5A 0.25 .. 10.00 A 0.50 A
8107 ΣI FACTOR Measurem.Superv 0.00 .. 0.95 0.10 Summated Current Monitoring
Factor
8108 SUM.thres. U Measurem.Superv 10 .. 200 V 10 V Summation Thres. for Volt. Moni-
toring
8109 SUM.Fact. U Measurem.Superv 0.60 .. 0.95 ; 0 0.75 Factor for Volt. Sum. Monitoring
8201 TRIP Cir. SUP. TripCirc.Superv OFF
ON
OFF TRIP Circuit Supervision
8501 MEAS. VALUE 1> Threshold Disabled
P
Q
Delta P
U1
U2
I0
I1
I2
PHI
Disabled Measured Value for Threshold
MV1>
8502 THRESHOLD MV1> Threshold -200 .. 200 % 100 % Pickup Value of Measured Value
MV1>
8503 MEAS. VALUE 2< Threshold Disabled
P
Q
Delta P
U1
U2
I0
I1
I2
PHI
Disabled Measured Value for Threshold
MV2<
8504 THRESHOLD MV2< Threshold -200 .. 200 % 100 % Pickup Value of Measured Value
MV2<
8505 MEAS. VALUE 3> Threshold Disabled
P
Q
Delta P
U1
U2
I0
I1
I2
PHI
Disabled Measured Value for Threshold
MV3>
8506 THRESHOLD MV3> Threshold -200 .. 200 % 100 % Pickup Value of Measured Value
MV3>
8507 MEAS. VALUE 4< Threshold Disabled
P
Q
Delta P
U1
U2
I0
I1
I2
PHI
Disabled Measured Value for Threshold
MV4<
8508 THRESHOLD MV4< Threshold -200 .. 200 % 100 % Pickup Value of Measured Value
MV4<
8509 MEAS. VALUE 5> Threshold Disabled
P
Q
Delta P
U1
U2
I0
I1
I2
PHI
Disabled Measured Value for Threshold
MV5>
Addr. Parameter Function C Setting Options Default Setting Comments