A.7 Settings
387
7UM61 Manual
C53000-G1176-C127-3
8510 THRESHOLD MV5> Threshold -200 .. 200 % 100 % Pickup Value of Measured Value
MV5>
8511 MEAS. VALUE 6< Threshold Disabled
P
Q
Delta P
U1
U2
I0
I1
I2
PHI
Disabled Measured Value for Threshold
MV6<
8512 THRESHOLD MV6< Threshold -200 .. 200 % 100 % Pickup Value of Measured Value
MV6<
8601 EXTERN TRIP 1 External Trips OFF
ON
Block relay
OFF External Trip Function 1
8602 T DELAY External Trips 0.00 .. 60.00 sec; 1.00 sec Ext. Trip 1 Time Delay
8701 EXTERN TRIP 2 External Trips OFF
ON
Block relay
OFF External Trip Function 2
8702 T DELAY External Trips 0.00 .. 60.00 sec; 1.00 sec Ext. Trip 2 Time Delay
8801 EXTERN TRIP 3 External Trips OFF
ON
Block relay
OFF External Trip Function 3
8802 T DELAY External Trips 0.00 .. 60.00 sec; 1.00 sec Ext. Trip 3 Time Delay
8901 EXTERN TRIP 4 External Trips OFF
ON
Block relay
OFF External Trip Function 4
8902 T DELAY External Trips 0.00 .. 60.00 sec; 1.00 sec Ext. Trip 4 Time Delay
9011A RTD 1 TYPE RTD-Box Not connected
Pt 100
Ni 120
Ni 100
Pt 100 RTD 1: Type
9012A RTD 1 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Winding RTD 1: Location
9013 RTD 1 STAGE 1 RTD-Box -50 .. 250 °C; 100 °C RTD 1: Temperature Stage 1
Pickup
9014 RTD 1 STAGE 1 RTD-Box -58 .. 482 °F; 212 °F RTD 1: Temperature Stage 1
Pickup
9015 RTD 1 STAGE 2 RTD-Box -50 .. 250 °C; 120 °C RTD 1: Temperature Stage 2
Pickup
9016 RTD 1 STAGE 2 RTD-Box -58 .. 482 °F; 248 °F RTD 1: Temperature Stage 2
Pickup
9021A RTD 2 TYPE RTD-Box Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 2: Type
9022A RTD 2 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 2: Location
9023 RTD 2 STAGE 1 RTD-Box -50 .. 250 °C; 100 °C RTD 2: Temperature Stage 1
Pickup
9024 RTD 2 STAGE 1 RTD-Box -58 .. 482 °F; 212 °F RTD 2: Temperature Stage 1
Pickup
9025 RTD 2 STAGE 2 RTD-Box -50 .. 250 °C; 120 °C RTD 2: Temperature Stage 2
Pickup
9026 RTD 2 STAGE 2 RTD-Box -58 .. 482 °F; 248 °F RTD 2: Temperature Stage 2
Pickup
9031A RTD 3 TYPE RTD-Box Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 3: Type
Addr. Parameter Function C Setting Options Default Setting Comments
www . ElectricalPartManuals . com