388
7UM61 Manual
C53000-G1176-C127-3
9032A RTD 3 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 3: Location
9033 RTD 3 STAGE 1 RTD-Box -50 .. 250 °C; 100 °C RTD 3: Temperature Stage 1
Pickup
9034 RTD 3 STAGE 1 RTD-Box -58 .. 482 °F; 212 °F RTD 3: Temperature Stage 1
Pickup
9035 RTD 3 STAGE 2 RTD-Box -50 .. 250 °C; 120 °C RTD 3: Temperature Stage 2
Pickup
9036 RTD 3 STAGE 2 RTD-Box -58 .. 482 °F; 248 °F RTD 3: Temperature Stage 2
Pickup
9041A RTD 4 TYPE RTD-Box Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 4: Type
9042A RTD 4 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 4: Location
9043 RTD 4 STAGE 1 RTD-Box -50 .. 250 °C; 100 °C RTD 4: Temperature Stage 1
Pickup
9044 RTD 4 STAGE 1 RTD-Box -58 .. 482 °F; 212 °F RTD 4: Temperature Stage 1
Pickup
9045 RTD 4 STAGE 2 RTD-Box -50 .. 250 °C; 120 °C RTD 4: Temperature Stage 2
Pickup
9046 RTD 4 STAGE 2 RTD-Box -58 .. 482 °F; 248 °F RTD 4: Temperature Stage 2
Pickup
9051A RTD 5 TYPE RTD-Box Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 5: Type
9052A RTD 5 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 5: Location
9053 RTD 5 STAGE 1 RTD-Box -50 .. 250 °C; 100 °C RTD 5: Temperature Stage 1
Pickup
9054 RTD 5 STAGE 1 RTD-Box -58 .. 482 °F; 212 °F RTD 5: Temperature Stage 1
Pickup
9055 RTD 5 STAGE 2 RTD-Box -50 .. 250 °C; 120 °C RTD 5: Temperature Stage 2
Pickup
9056 RTD 5 STAGE 2 RTD-Box -58 .. 482 °F; 248 °F RTD 5: Temperature Stage 2
Pickup
9061A RTD 6 TYPE RTD-Box Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 6: Type
9062A RTD 6 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 6: Location
9063 RTD 6 STAGE 1 RTD-Box -50 .. 250 °C; 100 °C RTD 6: Temperature Stage 1
Pickup
9064 RTD 6 STAGE 1 RTD-Box -58 .. 482 °F; 212 °F RTD 6: Temperature Stage 1
Pickup
9065 RTD 6 STAGE 2 RTD-Box -50 .. 250 °C; 120 °C RTD 6: Temperature Stage 2
Pickup
9066 RTD 6 STAGE 2 RTD-Box -58 .. 482 °F; 248 °F RTD 6: Temperature Stage 2
Pickup
9071A RTD 7 TYPE RTD-Box Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 7: Type
Addr. Parameter Function C Setting Options Default Setting Comments