A.7 Settings
389
7UM61 Manual
C53000-G1176-C127-3
9072A RTD 7 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 7: Location
9073 RTD 7 STAGE 1 RTD-Box -50 .. 250 °C; 100 °C RTD 7: Temperature Stage 1
Pickup
9074 RTD 7 STAGE 1 RTD-Box -58 .. 482 °F; 212 °F RTD 7: Temperature Stage 1
Pickup
9075 RTD 7 STAGE 2 RTD-Box -50 .. 250 °C; 120 °C RTD 7: Temperature Stage 2
Pickup
9076 RTD 7 STAGE 2 RTD-Box -58 .. 482 °F; 248 °F RTD 7: Temperature Stage 2
Pickup
9081A RTD 8 TYPE RTD-Box Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 8: Type
9082A RTD 8 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 8: Location
9083 RTD 8 STAGE 1 RTD-Box -50 .. 250 °C; 100 °C RTD 8: Temperature Stage 1
Pickup
9084 RTD 8 STAGE 1 RTD-Box -58 .. 482 °F; 212 °F RTD 8: Temperature Stage 1
Pickup
9085 RTD 8 STAGE 2 RTD-Box -50 .. 250 °C; 120 °C RTD 8: Temperature Stage 2
Pickup
9086 RTD 8 STAGE 2 RTD-Box -58 .. 482 °F; 248 °F RTD 8: Temperature Stage 2
Pickup
9091A RTD 9 TYPE RTD-Box Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 9: Type
9092A RTD 9 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 9: Location
9093 RTD 9 STAGE 1 RTD-Box -50 .. 250 °C; 100 °C RTD 9: Temperature Stage 1
Pickup
9094 RTD 9 STAGE 1 RTD-Box -58 .. 482 °F; 212 °F RTD 9: Temperature Stage 1
Pickup
9095 RTD 9 STAGE 2 RTD-Box -50 .. 250 °C; 120 °C RTD 9: Temperature Stage 2
Pickup
9096 RTD 9 STAGE 2 RTD-Box -58 .. 482 °F; 248 °F RTD 9: Temperature Stage 2
Pickup
9101A RTD10 TYPE RTD-Box Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD10: Type
9102A RTD10 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD10: Location
9103 RTD10 STAGE 1 RTD-Box -50 .. 250 °C; 100 °C RTD10: Temperature Stage 1
Pickup
9104 RTD10 STAGE 1 RTD-Box -58 .. 482 °F; 212 °F RTD10: Temperature Stage 1
Pickup
9105 RTD10 STAGE 2 RTD-Box -50 .. 250 °C; 120 °C RTD10: Temperature Stage 2
Pickup
9106 RTD10 STAGE 2 RTD-Box -58 .. 482 °F; 248 °F RTD10: Temperature Stage 2
Pickup
9111A RTD11 TYPE RTD-Box Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD11: Type
Addr. Parameter Function C Setting Options Default Setting Comments
www . ElectricalPartManuals . com