Alarm, error and system messages
8.2 LED displays
SIRIUS 3RN2 thermistor motor protection relay
Manual, 10/2016, A5E34244868002A/RS-AA/001
55
The table below applies to the following modules:
3RN2011-.BA30
3RN2011-.BW30
3RN2012-.BA30
3RN2012-.BW30
3RN2012-.BW31
3RN2013-.BA30
3RN2013-.BW30
3RN2013-.GW30
READY
TRIPPED
Meaning
ON ON
Self-test is being performed (on startup or after pressing the
TEST/RESET button > 2 s)
Temperature above the permitted limit
ON
flickering
Short circuit in the sensor circuit
ON
flashing
Wire break in the sensor circuit
ON OFF Temperature below the permitted limit
OFF
flashing
Device in system STOP following inadequate supply voltage
1)
OFF OFF
No supply voltage, or
Device defective
1)
NOTICE
Restart required
The device must be disconnected from the supply voltage for at least 1 s before restarting
the system.