Alarm, error and system messages
8.2 LED displays
SIRIUS 3RN2 thermistor motor protection relay
Manual, 10/2016, A5E34244868002A/RS-AA/001
55
The table below applies to the following modules:
● 3RN2011-.BA30
● 3RN2011-.BW30
● 3RN2012-.BA30
● 3RN2012-.BW30
● 3RN2012-.BW31
● 3RN2013-.BA30
● 3RN2013-.BW30
● 3RN2013-.GW30
ON ON
• Self-test is being performed (on startup or after pressing the
TEST/RESET button > 2 s)
• Temperature above the permitted limit
Short circuit in the sensor circuit
Wire break in the sensor circuit
ON OFF Temperature below the permitted limit
Device in system STOP following inadequate supply voltage
1)
OFF OFF
• No supply voltage, or
• Device defective
1)
The device must be disconnected from the supply voltage for at least 1 s before restarting
the system.