Technical data
14.3 3RW40
SIRIUS 3RW30 / 3RW40
152 Manual, 10/2018, NEB535199502000/RS-AB/005
14.3.16
Recommended filters
Soft starter type
Rated cur-
rent
of soft starter
Recommended filter
1)
Voltage range 200 ... 480 V
Filter type
Rated current of
filter
Connecting termi-
nals
A
A
mm
2
3RW4036 45 4EF1512-1AA10
⇒ B84143B0050R110 (http://www.epcos.com)
50 16
3RW4037 63 4EF1512-2AA10
⇒ B84143B0066R110 (http://www.epcos.com)
66 25
3RW4038 72 4EF1512-3AA10
⇒ B84143B0090R110 (http://www.epcos.com)
90 25
3RW4046 80 4EF1512-3AA10
⇒ B84143B0090R110 (http://www.epcos.com)
90 25
3RW4047 106 4EF1512-4AA10
⇒ B84143B0120R110 (http://www.epcos.com)
120 50
1) The interference suppression filter is used to remove conducted interference in the main circuit. The field
-conducted
emissions meet radio suppression level B. The filter selection applies under standard conditions: 10 starts per hour,
start time 4 s at 300% I
e
.
14.3.17
Types of coordination
The type of coordination according to which the motor feeder with soft starter is mounted
depends on the application-specific requirements. Normally, fuseless mounting (combination
of motor starter protector and soft starter) is sufficient. If type of coordination 2 needs to be
fulfilled, semiconductor fuses must be fitted in the motor feeder.
Type of coordination 1 in accordance with IEC 60947
-4-1:
The device is defective following a short
-circuit failure and therefore unsuitable for fur-
ther use (personnel and equipment must not be put at risk).
Type of coordination 2 in accordance with IEC 60947
-4-1:
The device is suitable for further use following a short
-circuit failure (personnel and
equipment must not be put at risk)
.
The type of coordination only refers to soft starters in conjunction with the stipulated
protective device (motor starter protector / fuse), not to additional components in the
feeder.