SIRIUS 3RW30 / 3RW40 
Manual, 10/2018, NEB535199502000/RS-AB/005 
85 
 
The SIRIUS 3RW30 and 3RW40 electronic soft starters are designed for normal starting. A 
larger size may need to be selected for longer ramp-up times or a higher starting frequency.  
An appropriately dimensioned SIRIUS 3RW40 or 3RW44 soft starter should be chosen for 
startup processes with motor ramp-up times > 20 s. 
The motor feeder between the soft starter and motor must not contain any capacitive 
elements (such as compensation systems). Active filters must not be operated in 
combination with soft starters. 
All elements of the main circuit (such as fuses and switching devices) must be dimensioned 
for direct starting and according to the on-site short-circuit conditions, and ordered 
separately. 
The harmonic component load of the starting current must be taken into consideration when 
selecting motor starter protectors (trip selection). 
 
Note 
Voltage dips generally occur in all start modes (direct starting, wye
-delta starting, soft 
-phase motor is switched on. The infeed transformer must always be 
dimensioned so that the voltage dip at the motor startup remains w
ithin the permissible 
tolerance. If the infeed transformer is insufficiently dimensioned, the control voltage should 
be supplied from a separate circuit (independently of the main voltage) in order to prevent 
the voltage dip from disconnecting the 3RW.
 
 
Note 
All elements of the main circuit (such as fuses, motor starter protectors, and switching 
devices) must be dimensioned for direct starting and according to the on
-site short-circuit 
conditions, and ordered separately.
 
-delta starters are exchanged for soft starters in an existing system, you should check 
the fuse ratings in the feeder in order to avoid false tripping. This is particularly important in 
connection with heavy
-duty starting or if the fuse that is installed has already been operated 
close to the thermal tripping limit with the wye
-delta assembly. 
For recommended fuse and motor starter protector ratings for the feeder with soft starter, 
refer to chapter 
Technical data (Page 127).