5.6 Functions of the outputs
SIRIUS 3RW30 / 3RW40
54 Manual, 10/2018, NEB535199502000/RS-AB/005
5.6
Functions of the outputs
5.6.1
3RW30: Output terminal 13 / 14 ON
The potential-free output contact at terminal 13/14 (ON) closes if a signal is present at
terminal 1 (IN); it remains closed until the start command is removed.
The output can be used, for instance, to control a line contactor connected upstream or to
implement latching if you selected pushbutton control. For recommended circuits, refer to
chapter Typical circuit diagrams (Page 161).
For a state diagram of the contact in the various operating states, refer to chapter Messages
and diagnosis (Page 57).
5.6.2
3RW40: Output terminals 13 / 14 ON / RUN and 23 / 24 BYPASSED
ON
The potential-free output contact at terminal 13/14 (ON) closes if a signal is present at
terminal 1 (IN); it remains closed until the start command is removed (factory default). The
ON function can be used, for instance, as a latching contact if you selected pushbutton
control.