Typical circuit diagrams 
  16.10 3RW and contactor for emergency starting 
SIRIUS 3RW30 / 3RW40 
Manual, 10/2018, NEB535199502000/RS-AB/005 
191 
 
Figure 16-31  Wiring of the control circuit 3RW405 - 3RW407 
(1) For permissible main and control voltage values (dependent on article number), refer to 
chapter Technical data (Page 127). 
 
(2) Automatic restart. Can result in death, serious injury, or property damage. 
The start command (e.g. issued by the PLC or switch S1) must be reset prior to issuing a 
RESET command because the motor attempts to restart again automatically following this 
RESET command if a start command is still present. This particularly applies if the motor 
protection has tripped. For safety reasons, you are advised to integrate the group fault 
output (terminals 95 and 96) in the controller. 
(3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type 
of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter 
Technical data (Page 127). 
For the optional thermistor motor protection evaluation, refer to Typical circuit for the optional 
thermistor motor protection evaluation (Page 161).