Circuit Examples
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 02
8-3
8.1.2 3RW44 in Standard Circuit with Line Contactor and Control via PLC
1) For permissible values for main and control voltage, refer to technical data, pages 9-7 to 9-11.
2) Caution: risk of restart!
The start command (e.g. by the PLC) must be reset before a reset command is issued, since an automatic
restart is executed when a start command is pending after the reset command is issued. This especially
applies to motor protection tripping.
For safety reasons it is recommended to integrate the group error output (terminals 95 and 96) into the
control.
Main circuit Control circuit
Standard circuit with optional main contactor Activation of an optional main contactor and activation via PLC
Q1
L3
L2
L1
G1
K1
F3
L1
L2
L3
T1 T2 T3
M1
NSB0_01495
V1U1 W1
M
PE
3~
(optional line contactor
if floating switching of the
motor is planned)
1)
3/N/PE 400 V AC , 50 Hz
13
14
23
24
33
34
95 9896
+
T1 T2IN4IN3IN2IN1L-L+A1
A2
N
PE
PE
G1
K1
NSB0_01496
F2
+24 V DC
M
Switch-on duration
Motor right
Trip Reset
PLC outputs
PLC inputs
No action
No action
No action No action
Group error
PTC type A /
Thermoclick
(optional line contactor
if floating switching
of the motor is planned)
PS1
ResetStart
2)
1)
L1 1/N/PE 230 V AC , 50 Hz