Device Functions
SIRIUS 3RW44 manual
6-10 GWA 4NEB 535 2195-02 DS 02
Note 
Due to the high starting current of the motor, the error "Current limit exceeded" 
may occur in direct on-line starting mode. It may be necessary to select a larger 
dimensioned soft starter. 
Run-up recognition The soft starter features an internal run-up recognition. If a completed motor run-
up is recognized, the internal bypass contacts will close and the thyristors are 
bridged. 
6.2.6 Starting mode: motor heating
If IP54 motors are used outdoors, condensation occurs in the motor during 
cooler periods (e.g. overnight or in winter). This may lead to leakage currents or 
short circuits when the devices are switched on.
A pulsating DC current is fed into the motor winding to warm it up. 
If the "Motor heating" starting mode is selected, a heating capacity can be 
entered in the settings. This capacity should be chosen in such a way that the 
motor will not be damaged. The setting range for the heating capacity extends 
from 10 - 100 %. This corresponds to a motor current of approximately 5 - 30 % 
of the motor rated current. 
Typical applications for motor heating
Used e.g. in outdoor drives to minimize condensation inside the motor.
Caution 
May lead to damage to property. 
The motor heating starting mode is not a continuous operating mode. The motor 
must be equipped with a temperature sensor (Thermoclick/PTC) to ensure motor 
protection. The motor model with integrated electronic motor overload protection 
is not suitable for this kind of operation.