Circuit Examples
SIRIUS 3RW44 manual
8-8 GWA 4NEB 535 2195-02 DS 02
8.1.7 3RW44 in a Standard Circuit with Soft Start/Stop and Additional Slow Speed Function in both
Directions of Rotation with one Parameter Set
Note: parameterization
Set the control input functions to:
IN1: Motor right PS1
IN2: Motor left PS1
IN3: Slow speed mode
IN4: Trip/Reset (factory setting)
The slow speed parameters in parameter set 1 must be set. Motor right means rotation in line phase direction, motor left means rotation counter-clockwise to the line
phase direction.
Notice
The slow speed function is not suitable for continuous operation. The motor can overheat at slow speed during continuous operation.
Caution: risk of restart:
The start command must be reset before a reset command is issued, since an automatic restart is executed when a start command is pending after the reset
command is issued. This especially applies to motor protection tripping.
K1, K2, K3 = relays for contact multiplication, e.g. for 230 V AC operation: 3RS 1800-1BP00
I>> I>> I>>
Q1
U1
V1
W1
G1
L1 L2
L3
T1
T2
T3
M1
3/N/PE
L1
L2
L3
A1
A2
IN1 IN2 IN3
IN4
L-L+
T1
T2
PE
G1
F1
N
PE
Trip / Reset
1/N/PE
L1
G1
14
13
24
23
33
34
96
95
98
K3 K1
K2
24 V DC Out
S1
G
1
G
1
K1 K2
S2
G
1
K3
S2
S2
S2
M
3~
AC (230 V, 115 V, depending on device type), 50 Hz
Start
right
soft
start /
stop
Slow
right
Slow
left
External
acknow-
ledgement
No action
No action
Group error
On-time
AC (400 V - 690 V, depending on device type), 50 Hz
Latching
coordinate switch
e. g.
3SB12 08-7KW01
Start
slow
right
Start
slow
left
Start
right
soft start
Motor right PS1
Motor left PS 1
Slow speed mode
Contact multiplication
Thermistor
protection
input