Circuit Examples
SIRIUS 3RW44 manual
8-6 GWA 4NEB 535 2195-02 DS 02
8.1.5 3RW44 in an Inside Delta Circuit
Reversed direction of rotation in an inside delta circuit
1) For permissible main and control voltage values, refer to Technical Data, pages 9-7 to 9-11.
2) Caution: risk of restart!
The start command (e.g. by the PLC) must be reset before a reset command is issued, since an automatic
restart is executed when a start command is pending after the reset command is issued. This especially
applies to motor protection tripping.
For safety reasons it is recommended to integrate the group error output (terminals 95 and 96) into the
control.
Main circuit Control circuit
Option 1a: Option 1:
Activation via PLC
Main circuit
Option 1b:
Notice
Observe the wiring suggestions for the inside delta circuit on the main circuit page.
Faulty connection may lead to disturbances.
M
V1
W1
U2
U1
W2 V2
G1
NSB0_01497
L1 L2 L3
T1 T2 T3
Q1
F3
K1
3~
L3
L2
1)
L1 3/N/PE 400 V AC , 50 Hz
M1
PE
13 14 23 24 33 34 95 98
96
+
T1 T2IN4IN3IN2IN1L-L+A1
A2
N
PE
PE
G1
K1
NSB0_01496
F2
+24 V DC
M
Switch-on duration
Motor right
Trip Reset
PLC outputs
PLC inputs
No action
No action
No action
No action
Group error
PTC type A /
Thermoclick
(optional line contactor
if floating switching
of the motor is planned)
PS1
ResetStart
2)
G1
L1 L2 L3
T1 T2 T3
M1
NSB0_01499
M
V1
U1
W1
U2
W2 V2
PE
3~
Q1
L3
L2
1)
L1 3/N/PE 400 V AC , 50 Hz
K1