9.3.4 Conductor Cross-sections
1) When connecting cable lugs to DIN 46235 use 3RT19 56-4EA1 terminal cover for conductor cross-sections from
95 mm² to ensure phase spacing.
2) When connecting cable lugs to DIN 46234, the 3RT19 66-4EA1 terminal cover must be used for conductor cross-
sections of 240 mm² and more as well as DIN 46235 for conductor cross-sections of 185 mm² and more to keep
the phase clearance.
Type 3RW44 2. 3RW44 3., 3RW44 4. 3RW44 5.
Conductor cross-sections
Screw-type terminals Main conductor:
With box terminal 3RT19 55-4G (55 kW) 3RT19 66-4G
Front clamping point
connected
Finely stranded with end sleeve mm
2
16 ... 70 70 ... 240
Finely stranded without end sleeve mm
2
16 ... 70 70 ... 240
Stranded mm
2
16 ... 70 95 ... 300
Ribbon cable conductors
(number x width x thickness)
mm min.3x9x0.8,
max. 6 x 15.5 x 0.8
min.6x9x0.8
max. 20 x 24 x 0.5
AWG conductors, solid or stranded AWG 6...2/0 3/0...600kcmil
Rear clamping point
connected
Finely stranded with end sleeve mm
2
16 ... 70 120 ... 185
Finely stranded without end sleeve mm
2
16 ... 70 120 ... 185
Stranded mm
2
16 ... 70 120 ... 240
Ribbon cable conductors
(number x width x thickness)
mm min.3x9x0.8,
max. 6 x 15.5 x 0.8
min.6x9x0.8
max. 20 x 24 x 0.5
AWG conductors, solid or stranded AWG 6...2/0 250 ... 500 kcmil
Both clamping points
connected
Finely stranded with end sleeve mm
2
max. 1 x 50, 1 x 70 min. 2 x 50; max. 2 x 185
Finely stranded without end sleeve mm
2
max. 1 x 50, 1 x 70 min. 2 x 50; max. 2 x 185
Stranded mm
2
max. 2 x 70 max. 2 x 70; max. 2 x 240
Ribbon cable conductors
(number x width x thickness)
mm max. 2 x (6 x 15.5 x 0.8) max. 2 x (20 x 24 x 0.5)
AWG conductors, solid or stranded AWG max. 2 x 1/0 min. 2 x 2/0;
max. 2 x 500 kcmil
Terminal screws M10 (hexagon socket, A/F4) M12 (hexagon socket, A/F5)
-Pickup torque 10 ... 12 20 ... 22
90 ... 110 180 ... 195
Screw-type terminals Main conductor:
With box terminal 3RT19 56-4G
Front or rear
clamping point
connected
Finely stranded with end sleeve mm
2
16 ... 120
Finely stranded without end sleeve mm
2
16 ... 120
Stranded mm
2
16 ... 120
Ribbon cable conductors
(number x width x thickness)
mm min.3x9x0.8
max. 6 x 15.5 x 0.8
AWG conductors, solid or stranded AWG 6 ... 250 kcmil
Both clamping points
connected
Finely stranded with end sleeve mm
2
max. 1 x 95, 1 x 120
Finely stranded without end sleeve mm
2
max. 1 x 95, 1 x 120
Stranded mm
2
max. 2 x 120
Ribbon cable conductors
(number x width x thickness)
mm max. 2 x (10 x 15.5 x 0.8)
AWG conductors, solid or stranded AWG max. 2 x 3/0
Screw-type terminals Main conductor:
Without box terminal/rail connection
Finely stranded with cable lug mm
2
16 ... 95
1)
50 ... 240
2)
50 ... 240
2)
Stranded with cable lug mm
2
25 ... 120
1)
70 ... 240
2)
70 ... 240
2)
AWG conductors, solid or stranded AWG 4 ... 250 kcmil 2/0...500kcmil 1/0 ... 500 kcmil
Connecting bar (max. width) mm
17 25 60
Terminal screws
M8 x 25 (A/F13) M10 x 30 (A/F17) M12 x 40
- Pickup torque NM
10 ... 14 14 ... 24 20 ... 35
lb. in
89 ... 124 124 ... 210 177 ... 310
NSB00479
NSB00480
NSB00481