EasyManua.ls Logo

Siemens SIRIUS 3RW44 - Page 133

Siemens SIRIUS 3RW44
153 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
General Technical Data
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 02
9-9
1) Current limit on soft starter set to 350 % I
M
.
2) For intermittent duty S4 with ON period = 70 %, T
u
= 40 °C, stand-alone installation vertical. The quoted
operating frequencies do not apply for automatic mode.
3) Maximum adjustable rated motor current I
M
, dependent on CLASS setting.
Type 3RW44 43 3RW44 44 3RW44 45 3RW44 46 3RW44 47
Power electronics
Rated operational current I
e
203 250 313 356 432
Load rating with rated operational current I
e
Acc. to IEC and UL/CSA for individual mounting
at 40/50/60 °C, AC-53a A
203/180/156 250/215/185 313/280/250 356/315/280 432/385/335
Smallest adjustable operational current I
M
For the motor overload protection
A
40 50 62 71 86
Power loss
In operation after completed soft starting with uninterrupted rated
operational current (40 °C) approx. W
89 110 145 174 232
During starting with current limit set to 350 %
I
M
(40 °C) W 3350 4000 4470 5350 5860
Permissible rated motor current and starts per hour
Normal starting (Class 5)
- Rated motor current I
M
1)
, starting time 5 s A 203 250 313 356 432
- Starts per hour
2)
1/h 41 41 41 41 39
- Rated motor current
I
M
1)3)
, starting time 10 s A 203 250 313 356 432
- Starts per hour
2)
1/h 20 20 19 17 16
Normal starting (Class 10)
- Rated motor current I
M
1)
, starting time 10 s A 203 250 313 356 432
- Starts per hour
2)
1/h 20 20 19 17 16
- Rated motor current
I
M
1)3)
, starting time 20 s A 203 250 313 356 432
- Starts per hour
2)
1/h 9 10 6 4 5
Normal starting (Class 15)
- Rated motor current I
M
1)
, starting time 15 s A 203 240 313 325 402
- Starts per hour
2)
1/h 13 13 10 13 11
- Rated motor current
I
M
1)3)
, starting time 30 s A 203 240 313 325 402
- Starts per hour
2)
1/h 3 6 1 2 1
For heavy starting (Class 20)
- Rated motor current I
M
1)
, starting time 20 s A 195 215 275 285 356
- Starts per hour
2)
1/h 10 10 10 10 10
- Rated motor current
I
M
1)3)
, starting time 40 s A 195 215 275 285 356
- Starts per hour
2)
1/h 1 5 1 3 1
For very heavy starting (Class 30)
- Rated motor current I
M
1)
, starting time 30 s A 162 180 220 240 285
- Starts per hour
2)
1/h 6 6 6 6 6
- Rated motor current
I
M
1)3)
, starting time 60 s A 162 180 220 240 285
- Starts per hour
2)
1/h 3 3 3 2 1

Table of Contents

Other manuals for Siemens SIRIUS 3RW44

Related product manuals