Mounting
7.3 Assembly and disassembly with different mounting systems
SIRIUS - SIRIUS 3RA load feeders
Manual, 09/2016, A5E03656507520A/RS-AB/003
109
/
Hook the feeder into the upper hooking position of the motor starter protector, and swivel
the feeder to the busbar adapter.
Screw the contactor tight diagonally into the openings provided using two M4 screws, plain
washers and spring washers.
Tightening torque: 1.5 ... 1.6 Nm
Insert the connecting cables into the corresponding main conductor terminals. Screw the
main conductor terminals tight.