Product description
3.2 Device versions
SIRIUS - SIRIUS 3RA load feeders
16 Manual, 09/2016, A5E03656507520A/RS-AB/003
Types of coordination
Fuseless load feeders up to 38 A (discrete configuration of individual devices with
connecting cables) and 32 A (pre-assembled complete devices or configuration with link
module) can be assembled in sizes S00 and S0.
An assembly up to 80 A (discrete configuration of individual devices with connecting cables)
and 65 A (as pre-assembled complete devices, or configuration with link module) is possible
in size S2.
An assembly up to 100 A (discrete configuration of individual devices with connecting
cables) is possible in size S3.
The table below lists the maximum power of the three-phase motor for pre-assembled
3RA2 complete devices based on the type of coordination at a voltage of 400 V AC.
Table 3- 1 Motor starter protector sizes
Size
Type of coordination
Power of three-phase motor
S00
1
0.06 to 7.5 kW
2 0.06 to 1.5 kW
S0
1
7.5 to 15 kW
2
1.5 to 15 kW
S2
1
15 kW … 30 / 37 kW (max. 65 A)
2
15 kW … 30 / 37 kW (max. 65 A)
Reference
More information ...
Can be found in...
About approved load feeders in the configuration manual entitled "Configuring SIRIUS Innovations
- Selection data for load feeders in fuseless and fused designs"
(Article Number: 3ZX1012-0RA21-1AC0)
Auxiliary contacts
The following auxiliary contacts are integrated into fuseless load feeders dependent upon
size.
Table 3- 2 Integrated auxiliary contacts
Size
Direct feeder
Reversing feeder
S00
1 NO contact is integrated in the contactor.
1 NC contact is integrated in the contactor.
S0
1 NO contact and 1 NC contact are integrated
in the contactor. The user can decide how the
NC contact is assigned.
1 NO contact and 1 NC contact are
integrated in the contactor. The NC contact
is assigned to the interlock.
S2
S3

Table of Contents

Other manuals for Siemens SIRIUS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIRIUS and is the answer not in the manual?

Siemens SIRIUS Specifications

General IconGeneral
Product brand nameSiemens
SeriesSIRIUS
Coil Voltage24V DC, 110V AC, 230V AC
Switching CapacityUp to 10A
Mounting TypeDIN rail
Product designationSIRIUS
Contact MaterialSilver alloy
Contact RatingVaries depending on the specific SIRIUS relay model (e.g., 6 A at 250 V AC, 10 A at 250 V AC)
Switching VoltageVaries depending on the specific SIRIUS relay model (e.g., 250 V AC, 400 V AC)
Mechanical LifeUp to 10 million operations
Electrical LifeUp to 100, 000 operations
Operating Temperature-25°C to +55°C
Protection ClassIP20
Size of relay baseVaries depending on the specific SIRIUS relay model