SITRANS F M MAG 5000/6000
Operating Instructions, 12/2013, A5E02338368-002 35
5 Connecting
5
WARNING
Mains supply from building installation Class II
A switch or circuit breaker (Max. 15 A) must be installed in close proximity to the equipment
and within easy reach of the operator. It must be marked as the disconnecting device for
the equipment.
WARNING
Protective conductor terminal
The required cable is min. AGW16 or 1.5 Cu.
WARNING
Wire insulation
The insulation between the connected mains supply and 24 V AC/DC supply for the
flowmeter must at least be rated with double or reinforced insulation at mains voltage.
For field wiring installation: Ensure that the National Installation Code of the country in
which the flowmeters are installed is met.
Note
National installation code
Observe country specific installation directives for field wiring.