Alarm, error, and system messages
8.2 List of error numbers
SITRANS F M MAG 5000/6000
Operating Instructions, 12/2013, A5E02338368-002 55
8.2 List of error numbers
I2 - Add-on module
Applied
A new module has been applied to the system
I3 - Add-on module
Install
An add-on module is defect or has been removed.
This can be an internal add-on module
A less vital parameter in the transmitter has been
replaced by its default value
W20 - Totalizer 1
Reset manually
During initialisation the check of the saved totalizer
value has failed. It is not possible to rely on the
saved totalizer value anymore. The totalizer value
must be reset manually in order to rely on future
readings
W20 - Totalizer 2
Reset manually
During initialisation the check of the saved totalizer
value has failed. It is not possible to rely on the
saved totalizer value anymore. The totalizer value
must be reset manually in order to rely on future
readings
W21 - Pulse overflow
Adj. pulse settings
Actual flow is too big compared with pulse width and
volume/pulse
W22 - Batch timeout
Check installation
Duration of batching has exceeded a predefined
maximum time
W23 - Batch overrun
Check installation
Batch volume has exceeded a predefined maximum
overrun volume
W24 - Batch neg. flow
Check flow direction
Negative flow direction during batch
Flow is above Q
max
settings
P40 - SENSORPROM®
Insert/change
SENSORPROM
®
unit not installed
P41 - Parameter range
Switch off and on
A parameter is out of range. The parameter could
not be replaced by its default value. The error will
disappear at the next power-on