Modbus
register
Data type /
Size in bytes
Parameter Description Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
11404 Unsigned / 2 Register 1 Modbus register that
defines the parameter
to be logged. Only pa‐
rameter of type float or
unsigned can be log‐
ged.
65535: No logging
65535 - Read /
write
11405 Unsigned / 2 Register 2 Modbus register that
defines the parameter
to be logged. Only pa‐
rameter of type float or
unsigned can be log‐
ged.
65535: No logging
65535 - Read /
write
...
11493 Unsigned / 2 Register 90 Modbus register that
defines the parameter
to be logged. Only pa‐
rameter of type float or
unsigned can be log‐
ged.
65535: No logging
65535 - Read /
write
A.9.10 Simulation
A.9.10.1 Inputs and outputs
Channel 2 output current
Table A-118 Channel 2 output current
Modbus
register
Data type /
Size in bytes
Parameter Description Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
8825 Unsigned / 2 Simulation Enables or disables
simulation of channel 2
output current.
0
● 0: Disabled
● 1: Enabled
Read /
write
8826 Float / 4 Simulated value Current value that is
output on the channel
when simulation is ena‐
bled.
0
[mA]
0 - 25 Read /
write
Modbus communication
A.9 Modbus holding registers tables
SITRANS FST030 (Modbus)
Operating Instructions, 08/2018, A5E37367739-AD 319