Modbus
register
Data type /
Size in bytes
Parameter Description Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
2742 Float / 4 Flow velocity Flow velocity simula‐
tion value
0.0
[m/s]
(8014)
-40.0 - 40.0 Read /
write
2752 Unsigned / 2 Liquid identifier Liquid identifier simula‐
tion value
0 - Read /
write
A.9.10.3 Alarms
Simulate alarms
Table A-135 Simulate alarms
Modbus
register
Data type /
Size in bytes
Parameter Description Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
6229 Unsigned / 2 Simulation
mode
Defines mode of alarm
simulation.
0
● 0: Off
● 1: Simulate alarm
item
● 2: Simulate alarm
class
Read /
write
6230 Unsigned / 4 Alarm items 1 Bitwise enabling of
alarms in alarm items 1.
Set bit means alarm
item simulation activa‐
ted. See Alarm items
(Page 293).
0 - Read /
write
6232 Unsigned / 4 Alarm items 2 Bitwise enabling of
alarms in alarm items 2.
Set bit means alarm
item simulation activa‐
ted. See Alarm items
(Page 293).
0 - Read /
write
6236 Unsigned / 4 Alarm items 4 Bitwise enabling of
alarms in alarm items 4.
Set bit means alarm
item simulation activa‐
ted. See Alarm items
(Page 293).
0 - Read /
write
6238 Unsigned / 4 Alarm items 5 Bitwise enabling of
alarms in alarm items 5.
Set bit means alarm
item simulation activa‐
ted. See Alarm items
(Page 293).
0 - Read /
write
Modbus communication
A.9 Modbus holding registers tables
SITRANS FST030 (Modbus)
Operating Instructions, 08/2018, A5E37367739-AD 327