EasyManua.ls Logo

Siemens SITRANS F US - Bacnet Protocol Implementation Conformance Statement

Siemens SITRANS F US
26 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SITRANS F US Clamp-on Communications Module
Compact Hardware Installation Instructions, 2/2014, A5E32586525-AD
23
BACnet Protocol Implementation Conformance
Statement
5
Typical BACnet Conformance Statement
Date:
January, 2012
Vendor Name:
Siemens Industry, Inc.
Product Name:
SITRANS F US Clamp
-On Ultrasonic
Flowmeters
Product Model Number:
Siemens Option Card
Application Software Version:
V6.11b (A)
Firmware Revision:
2.04.06
BACnet Protocol Revision:
1
Product Description:
Clamp-on ultrasonic flowmeter
BACnet Standardized Device Profile (Annex L):
BACnet Operator Workstation (B-OWS)
BACnet Advanced Operator Workstation (B-
AWS)
BACnet Operator Display (B-OD)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-
AAC)
BACnet Application Specific Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
List all BACnet Interoperability Building Blocks Supported (Annex K):
K.1.2 BIBB Data Sharing ReadProperty-B (DS-RP-B)
K.1.4 BIBB Data Sharing ReadPropertyMultiple-B (DS-RPM-B)
K.1.8 BIBB Data Sharing WriteProperty-B (DS-WP-B)
K.1.10 BIBB Data Sharing WritePropertyMultiple-B (DS-WPM-B)
K.1.12 BIBB Data Sharing COV-B (DS-COV-B)
K.2.2 BIBBAlarm and Event Notification Internal B (AE-N-I-B)
K.2.5 BIBBAlarm and Event ACK B (AE-ACK-B)
K.2.11 BIBBAlarm and Event Information B (AE-INFO-B)
K.5.1 BIBBDevice Management Dynamic Device Binding A (DM-DDB-A)
K.5.2 BIBBDevice Management Dynamic Device Binding B (DM-DDB-B)
K.5.4 BIBBDevice Management Dynamic Object Binding B (DM-DOB-B)
K.5.6 BIBBDevice Management Device Communication Control B (DM-DCC-B)
K.5.12 BIBBDevice Management Time Syncronization B (DM-TS-B)