PROFIsafe
1.5 PROFIsafe Configuration
SITRANS P, DS III PROFIsafe series
1-4 Supplement to Operating Instructions, 03/2006, A5E00732533-01
1.5.3 Configure device with HW Config
Procedure
1. You are in the "Catalog" view with the "standard" profile. Go to the device in the catalog:
"PROFIBUS-PA > Sensors > Pressure > SIEMENS > SITRANS P DSIII PROFIsafe"
2. Pull the following device onto "PA Master System" with Drag & Drop.
The "Properties" dialog box is opened.
3. Set the PROFIBUS address.
The device is displayed in HW Config with the default configurations.
4. Delete the default module of the device at Slot 1.
5. You are now in the "Catalog" view. Under the PROFIsafe device go to the fail-safe
configuration "F:Pressure\Level\Flow\Temp".
6. Pull the F-module onto Slot 1 with Drag & Drop.
7. Open the "Properties" dialog box of the catalog.
8. Check the PROFIsafe address, parameter "F_Dest_ADD".
Note:
You must set the PROFIsafe address, parameter "F_Dest_ADD" to the same value later
using the PDM table in the device.
9. Close the "Properties" dialog box of the catalog.
10. Click the "Save and compile" button.
11. Press the "Download to module" button.
1.5.4 Configure CFC
Procedure
1. You are in the "Catalog" window, "Libraries" tab.
2. Locate the block "F_PA_AI [FB356] in the "Failsafe Blocks" library.
3. Pull the block into the plan with Drag & Drop.
4. Set the parameter "Value", value type "Real" in the block "F_PA_AI" as follows:
– Click this parameter with the right mouse button.
– Select "Connect to Operand..." in the context menu.
A selection list of transfer rates is displayed.
– Connect the parameter value of the block "F_PA_AI" with the real value of the
configured device.
5. Press the "Compile program" button.