PROFIsafe
1.7 PROFIsafe Commissioning
SITRANS P, DS III PROFIsafe series
1-10 Supplement to Operating Instructions, 03/2006, A5E00732533-01
3. Press the button "Confirm inspection completed" within 60 seconds.
The PROFIsafe Commissioning State shows: "S4 = PROFIsafe operation mode"
4. Press the "Close" button.
Result
The "Continue PROFIsafe Commissioning" dialog box is closed.
The PROFIsafe device is in "S4" and is write protected accordingly.
1.7.3 Check write protection with SIMATIC PDM
Procedure
To check the write protection in the PROFIsafe Commissioning State, e.g. "S4", proceed as
follows:
1. Click on "Device > Extended write protection > Lock or unlock device" in the menu bar.
2. Make sure that the second option checkbox is active.
Note
Local operation
The write protection in the PROFIsafe Commissioning State "S4" restricts local operation.
The parameters that affect the local appearance of the display can be adjusted.