Figure 8-1 Standstill monitoring
8.4.13 Standstill time
Standstill monitoring checks whether the scales are correctly balanced. Scale standstill is
registered if the weight changes by less than a specified fluctuation in d (standstill value) over
a specified time (standstill time). Standstill monitoring is used in static scale mode (with the
following commands: zeroing, taring).
8.4.14 Standstill waiting time
Standstill waiting time is a maximum waiting time for standstill on execution of a command
which depends on standstill (taring, zeroing). A technology message is generated if the
command cannot be executed during the standstill waiting time because there is no standstill.
If the standstill waiting time is equal to zero, a command requiring standstill is rejected
immediately if there is no standstill.
Scale parameters and functions
8.4 DR 3 calibration parameters
SIWAREX WP321
Operating Instructions, 08/2019, A5E33715669A-AD 65