The air quality average value of 2 air quality sensors is available in RMS705B
(device 1). This value is sent as transmission object via an analog output and
handled by RMS705B (device 2).
Example 1
The following transmission and reception zone is engineered for the example:
Dat
a exchan
ge concept
RMS705B, devic
e 1 RMS705B, device 2 Value
Terminal Transmission
zone
Terminal Reception zone
N.Y1 1 N.X1 1 Air quality average
= Transmission
= Reception
Config
uratio
n
D
evice 1
Config
ure the
following in
RMS70
5B, device 1:
Main menu > Commissioning > Communication > LTE transmission zones >
Operating line Range Factory setting
N.Y1 1
Configure the following in RMS705B, device 2:
D
evice 2
Main menu > Commissioning > Extra configuration > Input identifier >
Operating line Range Factory setting
N.X1 ppm
Main menu > Commissioning > Communication > LTE reception zones >
Operating line Range Factory setting
N.X1 1
Config
uration diagra
m
X
KNX
N.Y1
zone 1
Unit 1 Unit 2
186 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en