Status Register
The Status Register provides WL status information to the MODBUS master. The Status Register is accessed using the following functions:
- 02 Read Input Status Discretes
- 04 Read Input Registers
Bit number WL
0, 1
Circuit breaker position
00 = disconnected position
01 = connected position
10 = test position
11 = circuit breaker not present
2, 3
Circuit breaker status
00 = not ready
01 = circuit breaker open
10 = circuit breaker closed
11 = circuit breaker tripped
4 Circuit Breaker is ready to close
5 Undervoltage release
6 Closing spring charged
7 Overload warning
8 Setpoints active
9 Warning(s) active
10 MODBUS "Write enable" input active
11 User input
12, 13, 14
Tr ip
000 = no trip
001 = overload trip
010 = instantaneous short-circuit trip
011 = short time delayed short-circuit trip
100 = ground-fault trip
101 = trip caused by extended protective function
110 = N conductor trip
15 Load shedding