10 – 5
10.4 Installing the remote Bell Alarm reset
10.4.1 Mounting remote reset solenoid and cut-off switch
- OPEN the circuit breaker and discharge the closing spring (page 23-2).
- Move the circuit breaker into the withdrawn position in the cradle (page 23-3).
- Remove front panel (page 23-4).
- Remove the trip unit (page 9-49).
NOTICE
Can only be used with automatic reclosing lockout reset.
The remote reset solenoid will otherwise be overloaded and damaged.
DANGER
Hazardous voltage.
Will cause death, serious personal injury, or equipment damage.
Turn off and lock out all power supplying this device before working on this device.
WARNING
High speed moving parts.
Can cause serious personal injury.
Discharge the closing spring before inspection and before carrying out any work on the circuit breaker.