12.8.2.6 Contact Ratings
12.8.3 Order numbers
Voltage
Maximum Current
Continuous Making Breaking
120 VAC 10 A 30 A 3 A
240 VAC 10 A 30 A 3 A
24 VDC 5 A 1.1 A 1.1 A
48 VDC 5 A 1.1 A 1.1 A
125 VDC 5 A 1.1 A 1.1 A
250 VDC 5 A 0.55 A 0.55 A
MOC Catalog No.
Mechanism Operated Auxiliary Contacts, cradle-mounted, 4 NO + 4 NC,
Test and connected position, for draw-out circuit breaker only, FS II
WLMOC
Mechanism Operated Auxiliary Contacts, cradle-mounted, 4 NO + 4 NC,
Connected position only, for draw-out circuit breaker only, FS II
WLMOCC
Mechanism Operated Auxiliary Contacts, cradle-mounted, 4 NO + 4 NC,
Test and connected position, for draw-out circuit breaker only, FS III
WLMOC3
Mechanism Operated Auxiliary Contacts, cradle-mounted, 4 NO + 4 NC,
Connected position only, for draw-out circuit breaker only, FS III
WLMOCC3