15 – 1
15 Locking devices
15.1 Key Locks
Padlocking provisions (page 15-16)
Key lock Manufacturer Application
1
Breaker-mounted
key lock
KIRK
SUPERIOR
To activate the locking device, the circuit breaker must be opened. If the circuit breaker is closed, the
locking device is blocked. The block is only effective when the key is removed. The key can only be
removed in "OPEN" position.
(page 15-2)
2
Cradle-mounted
key lock
KIRK
SUPERIOR
This cradle-mounted key lock prevents the closing of any circuit breaker installed in the cell which this
lock is installed. Up to two independent Kirk or Superior key locks may be installed.
To activate the lock, the circuit breaker must be open. If the circuit breaker is closed, the locking device
is blocked. The block is only effective if the key is withdrawn. The key can only be removed in the
"OPEN" position.
(page 15-4)
3
Racking handle
key lock
KIRK
SUPERIOR
Prevents drawing out of the racking handle. The circuit breaker is protected from being moved. The
block is only effective when the key is removed.
(page 15-11)
4
Bell Alarm and open
fuse lockout key lock
A lockable cover prevents resetting the Bell Alarm or open fuse lockout after the breaker trips.
(page 15-15)