23.7 Exchanging the primary disconnects
(1) Finger cluster
(2) Stab tip
23.7.1 Exchanging the finger cluster
- OPEN the circuit breaker and discharge the closing spring (page 23-2)
- Remove the circuit breaker from the cradle (page 23-3)
(1) Self-tapping M4 screw
DANGER
Hazardous voltage.
Will cause death, serious personal injury, or equipment damage.
Turn off and lock out all power supplying this device before working on this device.
(2)
(1)
6
7
8
9
10
(1)
PZ 2
3,2 Nm
28 lb-in
1
2
3
5
4
PZ 2