23 – 3
 23.1.2 Removing the circuit breaker from the cradle
Crank the circuit breaker into the disconnected position
- Unlock racking handle / withdraw racking handle  (page 6-3)
Push in the racking handle
Pull circuit breaker into withdrawn position and remove
 NOTICE
Racking Handle Damage.
Turning the racking handle beyond the stop will cause damage to the racking mechanism.
When the stop is reached, rotate the handle counter-clockwise until it can be stowed.
blue
Position indicator
red
green
Stop