9 – 88
Digital output modules with relay output provide changeover contacts at their outputs.
Settings
Digital output modules with rotary coding switch
Setting principle (page 9-81)
The delay time setting determines how long a signal of the trip unit must be present until the corresponding LED lights up and the signal is
set at the corresponding output.
Configurable digital output modules
Configurable digital output modules can be adjusted via:
- the test socket of the trip unit with the BDA
-the PROFIBUS-DP / MODBUS.
Indicators
(page 9-81)
Testing
(page 9-81)
Current carrying capacity of the outputs
Relay output
250 V AC, 12 A
25 V DC, 12 A
Terminal assignment 1 (TRIP)
L Signaling contact overload tripping
S
Signaling contact short-time delayed short-circuit
tripping
I Signaling contact instantaneous short-circuit tripping
G Signaling contact ground-fault tripping
G ALARM Signaling contact ground-fault alarm
N Signaling contact neutral conductor tripping
Delay time setting
TRIP 0 - 2 sec.
ALARM 0 - 2 sec.
Output assignment 2 (ALARM)
PRE TRIP
Signaling contact leading signal overload tripping
(delay time 0 sec.)
TU ERR Signaling contact ETU error
LD SHED Signaling contact load shedding (delay time 0 sec.)
LD REST Signaling contact load restore (delay time 0 sec.)
TEMP Signaling contact temperature alarm
I UNBAL Signaling contact phase unbalance current