EasyManua.ls Logo

Siemens UL 1066 - Page 93

Siemens UL 1066
334 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 – 13
Motor protection function
In the circuit breaker position t
sd
= 0.02 sec., a special protection function for electromotive drives is activated. It prevents the short-time
delayed short-circuit tripping from being activated during the switch-on current peak of electric motors. At the same time, a phase failure
protection is activated
(page 9-14) and the time constant for the internally calculated reproduction of the temperature rise and cooling
process is switched over from switchgear protection to motor protection.
Instantaneous short-circuit tripping I-tripping
If the current setting I
i
is exceeded, the circuit breaker is tripped instantaneously.
Ground-fault tripping – G-tripping
If the trip unit is equipped with a ground-fault protection module, loads can be protected against impermissibly high ground-fault currents.
Trip units ETU745 - 776 can be equipped with it optionally. Ground-fault protection modules (page 9-45)
The response value I
g
, together with the setting for the delay time t
g
, determines the shutdown of ground-fault currents.
If the zone selective interlocking (ZSI) (page 9-15) is used and the ZSI module is set to "S" or "S+G" the adjusted delay time t
g
is auto-
matically set to 100 ms provided that in the event of ground-fault the circuit breaker does not receive a blocking signal from a downstream
circuit breaker. In this case regardless of the adjusted t
g
value the circuit breaker will trip after 100 ms.
If a blocking signal exists the adjusted delay time t
g
is valid. For safety reasons after 3 s the blocking signal is terminated. Some trip units
can be switched over to an I
2
t-characteristic.
Setting values for I
i
ETU745 OFF: I
i
= I
CW
I
i
= (1.5 / 2.2 / 3 / 4 / 6 / 8 / 10 / 12 × I
n
MAX = 0.8 x I
CW
ETU748 I
i
> I
CW
ETU776 I
i
= 1.5 x I
n
- 0.8 x I
cs
; OFF : I
i
= I
CW
Setting values for I
g
Frame size
II III
A 100 A 400 A
B 300 A 600 A
C 600 A 800 A
D 900 A 1000 A
E 1200 A 1200 A
Setting values for t
g
ETU745 - 748 t
g
= 0.1 / 0.2 / 0.3 / 0.4 / 0.5 sec.
ETU776 t
g
= 0.1 - 0.5 sec.
M

Table of Contents

Related product manuals