9 – 25
"Parameter setting" mode
In this mode, the following parameters can be adjusted:
- load shedding
- load restore
- delay time for load shedding/load restore
- language setting for display
NOTICE
Circuit breaker may trip.
If the trip settings are changed while the breaker is closed (and under load) the breaker may trip.
Adjust parameters only when the circuit breaker is in the open position.
To access "Parameter setting" mode, press the following button(s):
In "Autoscroll" mode
Screens displayed in "Parameter setting" mode
Screen 1
Setting
Load shedding
Screen 2
Setting
Load restore
Screen 3
Setting
Delay time
Load shedding/load restore
Screen 4
Setting
Display language
XXXX may be ENGL or GERM
Screen 5
Parameter settings are being
changed, switches to "Auto
-
scroll" mode after 10 seconds
NOTE
When screen 1, 2, 3 or 4 is displayed and no key is pressed within 10 seconds, "Parameter setting" mode is canceled.
Any parameter changes performed are not accepted. Display switches back to "Autoscroll" mode
Change Parameters
Load.Shed..=.0000.A
=+ =-
.und. =Confirm
Change Parameters
Load.Restore=.0000.A
=+ =-
.und. =Confirm
Change Parameters
=+ =-
.und. =Confirm
tx..........=...00.s
Change Parameters
=+ =-
.und. =Confirm
Sprache/Lang=...XXXX
Changed.Parameter
being.saved,
wait.10s