9-26
4007ES Panel Programmer Manual (579-1167)
Custom Control, Continued
Suppression 
Release Use 
Cases 
Initial data window
• Program#: 3 
Note: It is always 3 on a 4007ES.
• Check Enhanced Power Supply because we have an IDNAC channel.
• Uncheck Cross Zone (Dual Detector).
Note: Without cross zone the audible notification automatically defaults to Fast March Time 
(March120).
Abort Logic Window
• Set Immediate Release (No Delay).
Timer Configurations
• Uncheck Manual Release to set it a 0.
• Uncheck Detector Release Delay to set it at 0.
Hazard Area Lists window
• Press Manual Release Points and select the manual release point at M1-11-0.
• Press Automatic Release Points and select Automatic Release Points at M1-18-0.
• Do not add any devices to Abort Switches.
• Do not add any devices to Release Warning Points.
• Press Suppression Dump Points and select SIG3 and M1-36-0.
• Press Release Notification Audible NACs and select SIG913.
• Press Release Notification Visible NACs and select SIG915.
Table 9-6 describes actions and their corresponding responses.
Table 9-6. Immediate Release, Actions and Responses
Action Response
First detector is 
triggered 
RELSIG turns on steady. RELVIS turns on. SUPRELS NAC turns on steady and 
SRP output turns on steady.