4007ES Operators Manual (579-1165)
TrueAlarm Service:
Tap the TrueAlarm Service button to generate a report which contains the following information:
• Device Number
• Custom Label
• Alarm Level (sensitivity level of the device)
• Average Value
• Current Value
• Percent of Alarm: Shows the current value for the sensor. Value is shown as a percentage of 100% (alarm). For
example, if the value shown is 9%, it means that the sensor is currently at 9% of the value required to trigger an
alarm.
• Peak Value: Shows the highest value that the sensor has reached. Value is shown as a percentage of 100%
(alarm). For example, if the value shown is 9%, it means that the peak value experienced by the sensor was 9% of
the value required to trigger an alarm.
• Current State: Possible values include Normal, Trouble, Dirty, Excessively Dirty, and Almost Dirty.
TrueAlert NAC Test:
Tap the TrueAlert NAC Test button to generate a report which contains the following information for each TrueAlert
device:
• Point ID
• Custom Label
• Device Type
• Candela
TrueAlert Status:
The TrueAlert Status Report can be created after the TrueNAC Voltage Drop Test is run.
Tap the TrueAlert Status button to access the Print TAlert Status screen. The All button can be used to generate the
report containing the status for all devices. The Last button can be used to generate a report containing the status of the
last test. The report contains the following information:
• Point ID
• Custom Label
Pass/Fail
TrueAlarm CO:
Tap the TrueAlarm CO button to generate a report with the following information regarding the TrueAlarm CO devices:
• Device Number (on the network)
• Custom Label (custom description of the device)
• Current Device Value (PPM)
• End-of-Life Date
• Device Status (Normal, Trouble)
Continued on next page
Report Menu, Continued

Other manuals for Simplex 4007ES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4007ES and is the answer not in the manual?

Simplex 4007ES Specifications

General IconGeneral
Model4007ES
CategoryFire Alarms
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity RangeUp to 93% RH, non-condensing
Display4.3-inch color touchscreen
Power Supply120/240 VAC, 50/60 Hz
Network ConnectivityEthernet, RS-232, RS-485
Addressable Points250
Communication ProtocolsMAPNET II
Notification Appliance Circuits4 NACs
Total Points250
AnnunciationYes
Max Devices250
Max Notification Circuits4
Communication PortsRS-232, USB