Figure 8: 4098-9684 Heat Detector LED Base Connections for Style B or D Initiating Circuits
Note:
1. Figure shows 4098-9830 Remote LED. If used, the 4098-9830 remote LED is polarized. Observe color-coded wiring.
2. Wire the Primary-1 and the Backup-2 lines in separate wire runs, and in compliance with local requirements.
3. For a Style D initiating circuit, wire according to the dotted lines and do not use an EOL resistor. If it is a Style B initiating circuit,
refer to the wiring diagrams provided with the system panel for the correct EOL resistor value.