Figure 13: MAPNET/IDNet addresses
4.4.5 Wiring
Sensor bases are connected to the fire alarm control panel using a single wire pair for the 4098-9770, 4098-9775, 4098-9776, 4098-9777,
4098-9780, 4098-9789, 4098-9792, 4098-9793, 4098-9766 (IDNet2 only), and 4098-9767 (IDNet2 only) and two pairs of wires for the
4098-9771, 4098-9772 4098-9773, 4098-9791 and 4098-9794.
Using Figure 14 as a reference, connect the bases to the MAPNET II/IDNet wire pair and 24V power, if used.
Important: For additions to existing installations, remove the power from the panel before wiring any bases to avoid damage to the
equipment.
Figure 14: Smoke/Heat sensor base connections
page 25 574-709 Rev. AP
4098 Detectors, Sensors, and Bases Application Manual