3.3.2 Wiring
All screw terminals accommodate 14 to 18 American Wire Gauge (AWG) solid or stranded wire. When tightening screws, the range of
torque is 8 to 12 inch pounds. Connect the wiring to the terminals shown in the following figure, Figure 4 through Figure 8 show typical
wiring applications for the 4098 bases.
CAUTION: Do not loop the wire under the terminals. Break the wire run to provide supervision of the connections.
Figure 4: Wiring and mounting the bases
Note:
1. Break off the plastic tab where indicated to engage the locking mechanism.
2. When the locking mechanism is engaged, insert a flat-head screwdriver in the slot indicated to release the detector from the
base.
3. Use the slotted hole indicated for the first screw when mounting the base.
page 14 574-709 Rev. AP