Figure 5: 4098-9788 Base connections for Style B or D initiating circuits
Table 5: Figure symbol reference
Symbol Reference
*
2120 Listed Fire Alarm Control Panel
4001 Listed Fire Alarm Control Panel
4002 Listed Fire Alarm Control Panel
4020 Listed Fire Alarm Control Panel
4100+ Listed Fire Alarm Control Panel
4100U Listed Fire Alarm Control Panel
4100ES Listed Fire Alarm Control Panel
4007ES Listed Fire Alarm Control Panel
4007ES hybrid Listed Fire Alarm Control Panel
4004 Listed Fire Alarm Control Panel
4005 Listed Fire Alarm Control Panel
4006 Listed Fire Alarm Control Panel
Note:
1. If used, the 4098-9830 Remote LED is polarized. Refer to Figure 8 to wire the remote LED to the heat detector. Observe color-
coded wiring.
2. Refer to the wiring diagrams provided with the system panel for the correct End-Of-Line (EOL) resistor value.
3. Wire the Primary-1 and the Backup-2 lines separate wire runs, and in compliance with local requirements.
4. For a Style D initiating circuit, wire according to the dotted lines and do not use EOL resistor.
5. Break the wires before connecting to Terminal 4 to maintain supervision. Do not loop the wire underneath Terminal 4.
page 15 574-709 Rev. AP
4098 Detectors, Sensors, and Bases Application Manual